<html> <head> <title>Rule 61:08:05:07 Low-water fuel cutoffs required.</title> <META NAME="Keywords" Content="Administrative Rules 61:08:05:07"> <META NAME="Description" Content="Administrative Rules 61:08:05:07 Low-water fuel cutoffs required."> <meta name=Generator content="Microsoft Office HTML Filter 2.0"> <meta http-equiv=Content-Type content="text/html; charset=windows-1252"> <meta name=Originator content="Microsoft Word 10"> <style> <!-- --> </style> </head> <body lang=EN-US> <div> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>61:08:05:07.&nbsp;&nbsp;Low-water fuel cutoffs required.</b> Each automatically fired steam or vapor system boiler shall be equipped with one or more automatic low-water fuel cutoffs wired in series with the limit controls. It shall be located to cut off the fuel supply automatically when the surface of the water falls to the lowest safe water line. Steam boilers equipped with the electrode type of low-water fuel cutoff are required to have an additional float-operated low-water fuel cutoff.</p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Source:</b> SL 1975, ch 16, §&nbsp;1; 5 SDR 61, effective January 28, 1979; 8 SDR 87, 8 SDR 134, effective July 1, 1982; 12 SDR 151, 12 SDR 155, effective July 1, 1986.</p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>General Authority:</b>SDCL <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29A-16">34-29A-16.</A></p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Law Implemented:</b>SDCL <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29A-17">34-29A-17</A>, <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29A-24">34-29A-24.</A></p> </div> </body> </html>