<html> <head> <title>Rule 61:08:09:19 Hydrostatic pretest -- Steam outlet requirements.</title> <META NAME="Keywords" Content="Administrative Rules 61:08:09:19"> <META NAME="Description" Content="Administrative Rules 61:08:09:19 Hydrostatic pretest -- Steam outlet requirements."> <meta name=Generator content="Microsoft Office HTML Filter 2.0"> <meta http-equiv=Content-Type content="text/html; charset=windows-1252"> <meta name=Originator content="Microsoft Word 10"> <style> <!-- --> </style> </head> <body lang=EN-US> <div> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>61:08:09:19.&nbsp;&nbsp;Hydrostatic pretest -- Steam outlet requirements.</b> Each threaded steam outlet from a power boiler, except to the water column, the fusible soft plug and the safety valve connections, must be fitted with a stop valve located as close as practicable to the boiler. Schedule 80 pipe must be used between the boiler and the first stop valve. If a globe valve is used, the inlet pressure must be under the disk of the valve.</p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Source:</b> 23 SDR 139, effective March 5, 1997.</p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>General Authority:</b>SDCL <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29A-14.1">34-29A-14.1.</A></p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Law Implemented:</b>SDCL <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29A-14.1">34-29A-14.1.</A></p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Cross-Reference:</b> Hydrostatic pretest -- Pipe requirements, §&nbsp;61:08:09:15.</p> </div> </body> </html>