<html> <head> <title>Rule 61:15:06:09 Portable fire extinguishers.</title> <META NAME="Keywords" Content="Administrative Rules 61:15:06:09"> <META NAME="Description" Content="Administrative Rules 61:15:06:09 Portable fire extinguishers."> <meta name=Generator content="Microsoft Office HTML Filter 2.0"> <meta http-equiv=Content-Type content="text/html; charset=windows-1252"> <meta name=Originator content="Microsoft Word 10"> <style> <!-- --> </style> </head> <body lang=EN-US> <div> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>61:15:06:09.&nbsp;&nbsp;Portable fire extinguishers.</b> Portable fire extinguishers must be provided on each level and near food processing equipment. Fire extinguishers must be a minimum of a 2A rating, as identified on the extinguisher label, and may serve no more than 2,000 square feet with a travel distance of not greater than 75 feet to an extinguisher.</p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Source:</b> 18 SDR 107, effective January 1, 1992; 23 SDR 32, effective September 11, 1996.</p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>General Authority:</b>SDCL <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29B-2">34-29B-2.</A></p> <p>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; <b>Law Implemented:</b>SDCL <A HREF="/statutes/DisplayStatute.aspx?Type=Statute&Statute=34-29B-2">34-29B-2.</A></p> </div> </body> </html>