CHAPTER 44:67:05
CONSTRUCTION STANDARDS
Section
44:67:05:01 Submittal of plans.
44:67:05:02 Procedure rooms and services.
44:67:05:03 Recovery rooms and services.
44:67:05:01. Submittal of plans. No construction may
begin until plans and specifications covering the construction of new buildings
and additions or material alterations to existing buildings are approved by the
department. A written narrative describing the intended use of the proposed
construction must accompany the plans and specifications.
Source:
33 SDR 107, effective December 26, 2006.
General
Authority: SDCL 34-23A-51.
Law
Implemented: SDCL 34-23A-51(1),(3),(5),(9).
44:67:05:02. Procedure rooms and services. Each abortion
facility shall be designed and equipped for the types of abortion procedures to
be performed.
Procedure rooms shall meet the
following requirements:
(1) A minimum area of 115
square feet (10.8 square meters);
(2) Equipped with a vinyl
floor surface;
(3) A work station and
handwashing sink. Handwashing facilities must be equipped with hands-free
controls and have a water supply spout mounted so that the discharge is a
minimum five inches above the rim of the fixture;
(4) Adequate lighting with
protective covers to prevent lamps from shattering; and
(5) Battery operated
emergency lighting.
Procedure services shall include:
(1) Provisions for
immediate post-procedure care; and
(2) Emergency drugs and
supplies specified by the medical staff.
Source:
33 SDR 107, effective December 26, 2006.
General
Authority: SDCL 34-23A-51.
Law
Implemented: SDCL 34-23A-51(5).
44:67:05:03. Recovery rooms and services. Each abortion
facility shall be designed and equipped for the types of abortion procedures to
be performed.
Recovery rooms shall meet the
following requirements:
(1) A minimum area of 45
square feet in each recovery station;
(2) Privacy curtains
surrounding each recovery station;
(3) A work station and
handwashing sink. Handwashing facilities shall be equipped with hand-free
controls and have a water supply spout mounted so that the discharge is a
minimum of five inches above the rim of the fixture;
(4) Adequate lighting with
protective covers to prevent lamps from shattering;
(5) An emergency call
system to summon staff; and
(6) Battery operated
emergency lighting.
Recovery services shall include:
(1) Provisions for
immediate post-procedure care; and
(2) Emergency drugs and
supplies specified by the medical staff.
Source:
33 SDR 107, effective December 26, 2006.
General
Authority: SDCL 34-23A-51.
Law
Implemented: SDCL 34-23A-51(5).