CHAPTER 44:70:10
CONSTRUCTION STANDARDS
Section
44:70:10:01 Application of chapter.
44:70:10:02 Resident rooms.
44:70:10:02.01 Modifications.
44:70:10:03 Service area in care units.
44:70:10:04 Dietary department.
44:70:10:05 Food preparation services and equipment.
44:70:10:06 Laundry.
44:70:10:07 Storage rooms.
44:70:10:08 Resident dining and recreation area.
44:70:10:09 Outside area.
44:70:10:10 Memory care unit locations.
44:70:10:11 Personnel facilities.
44:70:10:12 Engineering service and equipment areas.
44:70:10:13 Corridor restrictions.
44:70:10:14 Doors.
44:70:10:15 Ceiling heights.
44:70:10:16 Transferred.
44:70:10:17 Floor surface finish.
44:70:10:18 Wall and ceiling finish.
44:70:10:19 Elevators.
44:70:10:20 Steam and hot water systems.
44:70:10:21 Ventilating systems.
44:70:10:22 Filtration.
44:70:10:23 Ducts.
44:70:10:24 Food service ventilation.
44:70:10:25 Repealed.
44:70:10:26 Plumbing fixtures.
44:70:10:27 Water supply systems.
44:70:10:28 Vacuum breakers.
44:70:10:29 Hot water systems.
44:70:10:30 Drainage systems.
44:70:10:31 Electrical distribution system.
44:70:10:32 Emergency electrical services.
44:70:10:33 Lighting.
44:70:10:34 Receptacles or convenience outlets.
44:70:10:35 Staff call system.
44:70:10:36 Transferred.
44:70:10:37 Submittal of plans and specifications.
44:70:10:38 Pipe requirements.
44:70:10:39 Water recreation facilities.
44:70:10:01. Application of chapter. This chapter applies to any new facility and to any renovation, addition, or change in space use of any currently licensed existing facility. Accessible and usable accommodations must be available to the public, staff, and residents with disabilities.
Each facility shall comply with NFPA 101 Life Safety Code, 2012 edition.
Each facility providing off-site services shall comply with business occupancy standards and other occupancies standards as applicable for the use of the facility from NFPA 101 Life Safety Code, 2012 edition, chapter 38.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13.
References: NFPA 101 Life Safety Code, 2012 edition, National Fire Protection Association. Copies may be obtained at https://www.nfpa.org/Codes-and-Standards/All-Codes-and-Standards/List-of-Codes-and-Standards. Cost: $151.50.
44:70:10:02. Resident rooms. A resident room must meet the following requirements:
(1) A maximum room capacity not exceeding two residents;
(2) A minimum area, exclusive of toilet rooms, closets, lockers, wardrobes, or vestibules, of 120 square feet or 10.8 square meters in each one-bed room and 200 square feet or 18.58 square meters in each two-bed room. Any sleeping room designed as part of a suite of rooms shall have a minimum area of 100 square feet in each one-bed room and 140 square feet or 13 square meters in each two-bed room. The minimum dimension in a sleeping room may be not less than nine feet six inches or 2.74 meters;
(3) Privacy curtains shall be provided if requested by the resident. Privacy curtains or equivalent built-in devices, if installed, must provide full visual privacy that allows access to the toilet room and corridor without entering the roommate's space;
(4) A window sill not higher than three feet (0.91 meters) above the floor. The floor shall be above grade;
(5) A call cord at each bed for staff calling stations;
(6) A toilet room and lavatory. Each resident toilet room must be directly accessible for each resident without going through the general corridor. In remodeling projects, one toilet room with handsinks in a resident room may serve two resident rooms, but not more than four beds. For new construction, a toilet room may not be shared between resident rooms. All new resident toilet rooms must be wheelchair accessible;
(7) A wardrobe or closet for each resident with an area of at least five square feet or 0.465 square meters; and
(8) Each resident room door located not more than 200 feet or 45.72 meters from the staff station.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13(3).
44:70:10:02.01. Modifications. The department may approve a modification of the requirement in subdivision 44:70:10:02(8) if the following criteria are met:
(1) The facility fire alarm promptly alerts staff;
(2) The facility is equipped with an automatic sprinkler system, as defined in § 9.7, automatic sprinklers, of NFPA 101 Life Safety Code, 2012 edition;
(3) The facility is equipped with an automatic fire alarm dialer, as defined in § 9.6.4, Emergency Force Notification, of NFPA 101 Life Safety Code, 2012 edition, to summon the local fire department;
(4) The residents have an evacuation time that shows the residents are capable of evacuation in eight minutes or less;
(5) The facility is equipped with an approved call system in accordance with subdivision 44:70:02:17(3). Staff shall also carry a device that registers an audible and visual signal when the call system is activated;
(6) Residents are capable of self-preservation and require limited assistance of one staff;
(7) The facility has a plan in place to increase staffing during times of resident illnesses; and
(8) Healthcare personnel carry a device that can summon assistance from other staff.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13.
Reference: NFPA 101 Life Safety Code, 2012 edition, National Fire Protection Association. Copies may be obtained at https://www.nfpa.org/Codes-and-Standards/All-Codes-and-Standards/List-of-Codes-and-Standards. Cost: $151.50.
44:70:10:03. Service area in care units. Each care unit must contain a service area that includes the following:
(1) Staff station, staff office, or work area with convenient access to handwashing facilities;
(2) Communications;
(3) Storage for supplies and staff personal effects;
(4) Staff or public toilet room;
(5) Medicine room adjacent to the staff station with a sink, refrigerator, locked storage, and facilities for preparation and administration of medication;
(6) Clean linen storage area in an enclosed storage space;
(7) Equipment storage room on each resident wing or floor for storage of resident care equipment;
(8) Resident bathing facilities containing one shower, bathtub, or whirlpool for each 16 beds not individually served; and
(9) Janitor's closet for storage of housekeeping supplies and equipment that contains a floor receptor or service sink. The janitor's closet space and equipment may be incorporated into the laundry room.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13(3).
44:70:10:04. Dietary department. Construction, equipment, and installation of the dietary department must comply with §§ 44:02:07:01, 44:02:07:02, and 44:02:07:04 through 44:02:07:95, inclusive. The installation of food service equipment must comply with § 44:70:10:05 unless the facility uses a commercial service. If a commercial service is used, dietary areas and equipment must meet the requirements for sanitary storage, processing, and handling.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-1-17, 34-12-13(3).
Law Implemented: SDCL 34-12-13.
Cross Reference: Food Service Code, chapter 44:02:07.
44:70:10:05. Food preparation services and equipment. The dietary area must be completely cleanable by conventional methods. The location and design of the dietary area must enable convenient handling of incoming supplies, preparation of meals, including tray service, and disposal of rubbish and garbage. Equipment and space provided must include the following:
(1) In dietary areas serving 17 beds or more, a dishwashing area including a commercial dishwasher supplied with 180 degree Fahrenheit or 82 degrees centigrade rinse water or a chemical sanitizing cycle, a soiled dish table with sufficient work space, a garbage disposal, a garbage can, a clean dish table with room for at least three dish racks, and handwashing facilities. Dietary areas located in resident areas serving 16 residents or less may use an undercounter dishwasher;
(2) A dry food storage area with at least 1.5 linear feet or 0.46 meters of shelving 20 inches or 0.51 meters wide for each resident bed and a functional aisle;
(3) Refrigerated storage space providing at least 1.5 cubic feet or 0.042 cubic meters of refrigerated space and 0.5 cubic feet or 0.014 cubic meters of freezer space per resident bed with sufficient refrigerated storage space located within the food production area for convenient food preparation;
(4) Aisles within the dietary area not less than three feet or 0.91 meters wide. Aisles adjoining equipment locations with doors or aisles utilized for cart traffic shall be at least four feet or 1.22 meters wide;
(5) Pot and pan washing facilities, including a three-compartment sink, with 18 inch drainboards on both sides and drying and storage facilities for pots and pans;
(6) A vegetable preparation area with a two-compartment sink with drainboards on both sides;
(7) Cart storage areas;
(8) Waste disposal facilities;
(9) Janitor's closet with storage for housekeeping supplies and equipment and floor receptor or service sink;
(10) Food production equipment sized and designed to prepare a complete meal for the total bed complement and for personnel, guests, day-care residents, or other catering services;
(11) Food holding and transportation equipment capable of protecting food from contamination and of maintaining cold food at 41 degrees Fahrenheit or 5 degrees centigrade or below and hot food at 135 degrees Fahrenheit or 57.2 degrees centigrade or above during the total serving period;
(12) Ventilation equipment sized and designed to effectively remove steam, heat, cooking vapors, and grease from food production areas, dishwashing areas, and serving areas;
(13) Handwashing facilities that are convenient to each work area, consisting of hot and cold running water, towel dispenser with single-service towels or hand drying device and hand cleanser;
(14) In dietary areas serving 17 beds or more, a staff toilet facility within or conveniently located adjacent to the dietary area; and
(15) In dietary areas serving 17 beds or more, an ice maker with bin or self-dispensing ice maker. A built-in dispensing ice maker in a refrigerator may be used in any facility with a capacity of less than 17 beds. Any ice maker accessible to residents must be self-dispensing.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(2)(4).
Law Implemented: SDCL 34-12-13(1)(2)(4).
44:70:10:06.
Laundry. The laundry shall include the following:
(1) Soiled linen holding
room with a storage capacity of 1.75 square feet (0.1626 square meters) of
floor area for each bed, to be used for storage, sorting, and weighing of
soiled linen;
(2) Linen cart storage;
(3) Janitor's closet with
storage for housekeeping supplies and equipment and a floor receptor or service
sink convenient to the laundry;
(4) Storage for laundry
supplies;
(5) Lavatories conveniently
accessible to soiled, clean, and processing rooms; and
(6) Laundry processing room
with separate soiled and clean work areas with commercial equipment. Any
clothes dryer shall have a galvanized metal vent pipe for exhaust.
The space and equipment layout shall
be sized and designed to produce quality linen with a work flow that minimizes
potential for cross-contamination of clean linen by soiled linen, contaminated
equipment, contaminated air, or splash. The laundry department shall be capable
of processing 10 pounds (4.54 kilograms) of soiled linen for each bed during a
normal work day. Any modification to the standard may be made if the laundry
serves only an assisted living center or if the services are contracted to an
outside organization. Any modification shall be requested in writing by the
facility and approved by the department.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1) and (4).
Law
Implemented: SDCL 34-12-13(1) and (4).
44:70:10:07. Storage
rooms. There shall be at least 10 square feet (0.929 square meters) of
central storage provided for each bed. General storage shall be concentrated in
one area in the facility, but up to 50 percent of the general storage space may
be provided on the premises. Each resident shall be provided with an individual
closet with an area of at least five square feet (0.465 square meters) that is
directly connected to the resident room.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(3).
Law
Implemented: SDCL 34-12-13(3).
44:70:10:08. Resident
dining and recreation area. The total areas set aside for resident dining,
recreation, and other central use areas may not be less than 40 square feet
(3.71 square meters) for each bed and each adult day-care resident. The
resident dining space shall be at least 20 square feet (1.86 square meters) for
each bed or adult day resident. Additional space shall be provided for day-care
residents or residents if they participate in a day-care program. Storage shall
be provided for recreational equipment and supplies.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(3).
Law
Implemented: SDCL 34-12-13(3).
44:70:10:09. Outside area. Each memory care unit must have for the resident's use an outdoor area enclosed by a fence. The fence must extend to a minimum of six feet above grade level and be designed to be safe for resident contact. Hard surface walking paths shall be provided in the outside area. If the access to the outside area is through a required building exit, the area shall be large enough to allow movement of all affected residents 50 feet away from the building structure. A gate to exit the outside area must be provided.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(3)(14).
Law Implemented: SDCL 34-12-13(3)(14).
44:70:10:10. Memory care unit locations. Any memory care unit must be located at grade level and have direct access to an outside area.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(3).
Law Implemented: SDCL 34-12-13(1)(3).
44:70:10:11. Personnel facilities. The locker room for personnel must have lockers and a separate toilet room.
Source: 38 SDR 115, effective January 9, 2012; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-12-13(1).
Law Implemented: SDCL 34-12-13.
44:70:10:12. Engineering service and equipment areas. The requirements for engineering service and equipment areas for each facility are as follows:
(1) A maintenance shop with at least one room;
(2) A storage room for building maintenance supplies;
(3) A refuse room for trash storage that is conveniently located to the service entrance or exterior trash receptacles; and
(4) A yard equipment storage room or exterior building.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(3).
Law Implemented: SDCL 34-12-13(1)(3).
44:70:10:13. Corridor
restrictions. Drinking fountains, telephone booths, fire extinguisher
cabinets, and vending machines shall be located so that they do not project
into the required width of exit corridors. Handrails installed in corridors
shall return to the wall at the ends. Handrails shall be installed with the top
34 to 38 inches, inclusive, from the floor. Handrails shall be installed with
1½ inch spacing between the wall and the handrail.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1) and (3).
Law
Implemented: SDCL 34-12-13(1) and (3).
44:70:10:l4. Doors.
Any door to a resident room toilet or bathroom shall be equipped with hardware
that permits access in any emergency. A pocket or sliding door may not be
installed except on a clothes closet or restroom in a resident room. Any
hardware on a restroom pocket or sliding door shall provide for ease of
operation for a resident with limited mobility. Any door opening onto a
corridor, except an elevator door, shall be hinged on the side. Alcoves and
similar spaces which generally do not require doors are excluded from this
requirement. No door may swing into the corridor except a closet door. Any
cross-corridor door shall be provided with vision panels.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1) and (3).
Law
Implemented: SDCL 34-12-13(1) and (3).
44:70:10:15. Ceiling heights. The ceilings of corridors, storage rooms, resident toilet rooms, and other minor rooms may not be less than seven feet, eight inches or 2.34 meters. The ceilings of all other rooms may not be less than seven feet, ten inches or 2.39 meters.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(3).
Law Implemented: SDCL 34-12-13(1)(3).
44:70:10:16. Transferred to § 44:70:03:03.
44:70:10:17. Floor
surface finish. Floors shall be easily cleanable and shall have the wear
resistance appropriate for the location involved. Floors in kitchens and
related spaces shall be water-resistant. In all areas where floors are subject
to wetting, each floor shall have a nonslip finish. A walking surface that is
not flush with an adjacent surface shall be provided with a transition. A
change in level up to 1/8 inch may be vertical and without edge treatment.
Changes in level between 1/8 inch and 1/2 inch are to have bevel with a slope
no greater than 1:2. A change in level may not exceed 1/2 inch. Gaps in the
walking surface may not exceed 1/2 inch wide in the direction of travel.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1) and (3).
Law
Implemented: SDCL 34-12-13(1) and (3).
44:70:10:18. Wall
and ceiling finish. Walls shall be washable, and in the immediate area of
plumbing fixtures the finish shall be protected from water damage. Wall bases
in dietary areas shall be free of spaces that can harbor insects. Each dietary
ceiling shall be washable or easily cleanable. This requirement does not apply
to boiler rooms, mechanical and building equipment rooms, shops, and similar
spaces.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1) and (3).
Law
Implemented: SDCL 34-12-13(1) and (3).
44:70:10:19. Elevators.
If a resident's bed or a service such as recreation, resident dining, dietary,
laundry, central storage, or therapy rooms, is located on other than the first
floor, the facility shall have an electrical or electrohydraulic elevator. Each
elevator car and platform shall be constructed of noncombustible material,
except that material treated with fire retardant may be used if all exterior
surfaces of the car are covered with metal. The car door shall have a clear
opening of not less than three feet eight inches (1.12 meters). Each elevator
shall have automatic two-way leveling with accuracy within plus or minus 0.5
inch (0.01 meters). Each elevator, except a freight elevator, shall be equipped
with a two-way special service switch to permit cars to bypass all landing
button calls and to be dispatched directly to any floor.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(3) and (4).
Law
Implemented: SDCL 34-12-13(3) and (4).
44:70:10:20. Steam and hot water systems. Boilers must have the capacity to supply the normal requirements of all of the facility's systems and equipment. Supply and return mains and risers of space heating and process steam systems must be valved to isolate the various sections of each system. Each piece of equipment must be valved at the supply and return end. Boilers, smoke breeching, steam supply piping, high pressure steam return piping, and hot water space heating supply and return piping must be insulated with insulation having a flame spread index of twenty-five or less and a smoke emission rating of fifty or less using ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials, or equivalent test procedures.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023; 51 SDR 53, effective November 11, 2024.
General Authority: SDCL 34-12-13.
Law Implemented: SDCL 34-12-13.
Reference: ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials. Copies may be obtained at https://www.astm.org/e0084-23d.html. Cost: $119.00.
44:70:10:21. Ventilating systems. The ventilating systems must maintain temperatures, minimum air changes of outdoor air per hour, minimum total air changes, and relative humidities as follows:
(1) For all occupied areas, the facility shall be able to maintain a minimum temperature of seventy-five degrees Fahrenheit or 23.9 degrees centigrade at winter design conditions with a minimum of at least two total air changes per hour. Each air supply and air exhaust system must be mechanically operated. Any outdoor ventilation air intake, other than for an individual room unit, must be located as far away as practicable but not less than twenty-five feet or 7.62 meters from any plumbing vent stack and the exhaust from any ventilating system or combustion equipment. The bottom of any outdoor intake serving a central air system must be located as high as possible but not less than three feet or 0.91 meters above the ground level. Each mechanical ventilation system must be designed and balanced to provide make-up air and safe pressure relationships between adjacent areas to preclude the spread of infections and assure the health of the occupants. Each room supply air inlet, recirculation inlet, and exhaust air outlet must be located with the grill or diffuser opening not less than three inches or 0.08 meters above the floor. A corridor may not be used to supply air to or exhaust air from any room, except that air from a corridor may be used to ventilate a bathroom, a toilet room, or a janitor's closet opening directly on the corridor. Mechanical exhaust ventilation must be provided in all soiled areas, wet areas, toilet rooms, and clean storage rooms. In any unoccupied service area, ventilation may be reduced or discontinued if the health and comfort of the occupants are not compromised;
(2) Each cooking appliance, other than a microwave oven, must be provided with exhaust ventilation to the exterior of the building to remove cooking odors, heat, and moisture. Each cooking appliance installed in a resident room must have a recirculating fan equipped with a charcoal filter, or exhausted to the exterior;
(3) Each vehicle parking garage must be provided with carbon monoxide detection to activate exhaust ventilation of six air changes each hour or to open the garage door if the area of the garage is under one thousand square feet; and
(4) Each crawl space must be provided with mechanical ventilation of at least 0.5 air changes each day or be provided with open perimeter venting as required by the International Building Code, § 1203.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-12-13(1)(3)(4).
Law Implemented: SDCL 34-12-13.
Reference: International Building Code, 2012 edition. Copies may be obtained from International Code Council at https://shop.iccsafe.org/. Cost: $81.75.
44:70:10:22. Filtration. A ventilation system using a recirculated central air system must be equipped with a filter bed. The filter bed must be located upstream of the conditioning equipment and must have a minimum efficiency of MERV 7. These filter efficiencies must be warranted by the manufacturer and must be based on the ASHRAE 52.2, 2012 edition, American Society of Heating, Refrigeration, and Air Conditioning Engineers.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-12-13(1)(3)(4).
Law Implemented: SDCL 34-12-13.
Reference: "ASHRAE 52.2," 2012 edition, American Society of Heating, Refrigeration, and Air Conditioning Engineers. Copies are available at no cost at https://ierga.com/hr/wp-content/uploads/sites/2/2017/10/ASHRAE-52.2-2012.pdf.
44:70:10:23. Ducts. Each duct must be constructed of iron, steel, aluminum, or other approved metal or materials as defined in NFPA 101 Life Safety Code, 2012 edition, § 32.3.6.2.1. Duct linings, coverings, vapor barriers, and the adhesives used for applying them must have a flame spread index of not more than twenty-five and a smoke emission rating of not more than fifty using ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials. Each cold air duct must be insulated wherever necessary to maintain the efficiency of the system or to minimize condensation problems.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023; 51 SDR 53, effective November 11, 2024.
General Authority: SDCL 34-12-13.
Law Implemented: SDCL 34-12-13.
References: ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials. Copies may be obtained at https://www.astm.org/e0084-23d.html. Cost: $119.00.
NFPA 101 Life Safety Code, 2012 edition, National Fire Protection Association. Copies may be obtained at https://www.nfpa.org/product/nfpa-101-code/p0101code?Edition=2012&Language=English&Format=Softbound&type=digital. Cost: $160.00.
44:70:10:24. Food
service ventilation. The air from any dining area may be used to ventilate
the food preparation area only after it has been passed through a filter with
30 percent efficiency. Each exhaust hood in a food preparation center shall
have a minimum exhaust rate of 50 cubic feet a minute for each square foot
(0.25 cubic meters a second for each square meter) of hood face area. Each hood
over a cooking range shall be equipped with a fire extinguishing system
interconnected to shut off the fuel source. A cleanout opening shall be
provided every 20 feet (6.10 meters) in a horizontal exhaust duct system
serving a hood.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1), (3), and (4).
Law
Implemented: SDCL 34-12-13(1), (3), and (4).
44:70:10:25. Recirculated air systems. Repealed.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
44:70:10:26. Plumbing fixtures. The material used for plumbing fixtures must be of nonabsorptive acid-resistant material. Each lavatory and sink required in resident toilet rooms must have the water supply spout mounted so the discharge is a minimum of 2.5 inches or 0.064 meters above the rim of the fixture. Handwashing facilities used by medical and care staff and food handlers must have the water supply spout mounted so the discharge is a minimum of five inches or 0.13 meters above the rim of the fixture and be equipped with hands-free controls. A single lever device may be used. An aerator may not be used on a faucet spout. A paper towel dispenser or hand-drying device must be provided at each lavatory and sink used for handwashing.
Any shower stall not required to be of the wheelchair transfer or standard roll-in type must have curb heights not more than six inches above the finished floor. The shower floor elevation and bathroom finished floor elevation must be level, if possible, but the difference in elevation may not exceed three inches.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(3).
Law Implemented: SDCL 34-12-13(1)(3).
44:70:10:27. Water supply systems. Each water supply system must supply water to the fixtures and equipment on the upper floors at a minimum pressure of 15 pounds per square inch or 1055.9 kilograms per square meter during maximum demand periods. Each water service main, branch main, riser, and branch to a group of fixtures must be valved. Stop valves must be provided at each fixture. Hot, cold, and chilled water piping and waste piping on which condensation may occur must be insulated. Insulation of each cold and chilled water line must include an exterior vapor barrier.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(4)(14).
Law Implemented: SDCL 34-12-13(1)(4)(14).
44:70:10:28. Vacuum
breakers. An antisiphon device or backflow preventer shall be installed on
any hose bib and on any fixture to which a hose or tubing can be attached such
as a laboratory or a janitor's sink, bedpan flushing attachment, and a handheld
shower. Each antisiphon device or backflow preventer shall be installed on any
plumbing and equipment where any possibility exists for contamination of the
potable water supply.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1), (4), and (14).
Law
Implemented: SDCL 34-12-13(1), (4), and (14).
44:70:10:29. Hot water systems. Each hot water distribution system over 50 feet or 15.24 meters long must recirculate to provide hot water at each fixture at all times. The hot water heating equipment must have sufficient capacity to supply water at the temperatures and amounts indicated in the following:
(1) Three gallons an hour or 0.0033 liters a second for each bed;
(2) Two gallons an hour or 0.0020 liters a second for each bed for dietary use; and
(3) Two gallons an hour or 0.0020 liters a second per bed for laundry.
Each storage tank provided must be fabricated of noncorrosive metal or lined with noncorrosive material.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(4)(14).
Law Implemented: SDCL 34-12-13(1)(4)(14).
44:70:10:30. Drainage systems. Each drain line from a sink in which acid wastes may be poured must be fabricated from an acid resistant material. Any piping over food preparation centers, food service facilities, food storage areas, and other critical areas must be kept to a minimum and may not be exposed. Special precautions must be taken to protect these areas from possible leakage of necessary overhead piping systems. The building sewer system must discharge into a community sewerage system. If a building sewer system is not available, a facility providing sewage treatment that conforms to applicable local and state regulations is required.
Water from a roof system must be collected and discharged away from the building foundation. Rain gutters with downspouts and splash blocks must be provided for a pitched roof system. Provisions must be made to avoid having water accumulated on sidewalks and parking areas around the building.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(4)(14).
Law Implemented: SDCL 34-12-13(1)(4)(14).
Cross-Reference: Individual and small on-site wastewater systems, ch 74:53:01.
44:70:10:31. Electrical
distribution system. All material including equipment, conductors, controls
and signaling devices shall be installed to provide a complete electrical
system with the necessary characteristics and capacity to supply the electrical
facilities shown in the specifications or indicated on the plans. All materials
shall be listed as complying with applicable standards of Underwriters'
Laboratories, Inc., or other similarly established standards. Each circuit
breaker or fusible switch that provides disconnecting means and overcurrent
protection for a conductor connected to a switchboard and distribution panel
board shall be enclosed or guarded to provide a dead front type of assembly.
The main switchboard shall be located in a separate enclosure accessible only
to authorized persons. The switchboard shall be convenient for use, readily
accessible for maintenance, clear of traffic lanes, and in a dry ventilated
space devoid of corrosive fumes or gases. Each overload protective device shall
be designed for operating in the ambient temperature conditions. Each lighting
and appliance panel board shall be provided for each circuit on each floor.
This section does not apply to any emergency system circuit.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1), (3), and (4).
Law
Implemented: SDCL 34-12-13(1), (3), and (4).
44:70:10:32. Emergency
electrical service. A facility with 16 beds or less shall be equipped with
automatic emergency lighting for each exit way, staff work area, dining room,
medication room, dietary department, room where main electrical panels are located,
and power for the alarm system. A facility with 17 beds or larger shall be
equipped with an emergency electrical service that includes an automatic
generator set and automatic transfer switches serving emergency panels. A
facility with 17 beds or larger shall have automatic emergency lighting for
each exit way, staff work areas, dining room, medication room, dietary
department, medication room, room where main entrance electrical panels are
located, boiler room, and exterior lighting serving required exits. A facility
with 17 beds or larger shall have automatic emergency power for the fire alarm
system, electrical receptacle servicing computers containing resident care
records, telephone system, door alarms, and staff call system.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(1), (3), and (4).
Law
Implemented: SDCL 34-12-13(1), (3), and (4).
44:70:10:33. Lighting.
Any space occupied by people, machinery, and equipment within a building, any
approach to the building and parking lot shall have artificial lighting
approved by the department. Each resident's bedroom shall have general lighting
of at least 10 footcandles (0.929 lumens per square meter) and night lighting.
Plug-in night lights may be provided for each resident in a facility. If task
illumination is required, a light with an intensity of at least 30 footcandles
(2.79 lumens per square meter) at the work surface shall be provided for each
resident. Any resident's reading light and any other fixed light not switched
at the door shall have a switch control convenient for use at the luminarie.
Illumination of at least 100 footcandles (9.29 lumens per square meter) shall
be provided at the medication set-up area. Illumination of at least 50
footcandles (4.65 lumens per square meter) shall be provided at any activity
room work table. Illumination of at least 30 footcandles (2.79 lumens per square
meter) shall be provided in any dining area, in any physical and restorative
therapy area, and at any bathing facility.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(4), and (14).
Law
Implemented: SDCL 34-12-13(4), and (14).
44:70:10:34. Receptacles
or convenience outlets. Each resident bedroom shall have duplex receptacles
as follows: one on each side of the head of each bed; receptacles for
luminaries and motorized beds, if used; and one receptacle on another wall.
Duplex receptacles for general use shall be installed approximately 50 feet
apart in each corridor and within 25 feet of the end of the corridor.
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(4) and (14).
Law
Implemented: SDCL 34-12-13(4) and (14).
44:70:10:35. Staff
call system. A staff call system shall be provided for resident use in
accordance with subdivision 44:70:
Source:
38 SDR 115, effective January 9, 2012.
General
Authority: SDCL 34-12-13(4) and (14).
Law
Implemented: SDCL 34-12-13(4) and (14).
44:70:10:36. Transferred to § 44:70:03:04.
44:70:10:37. Submittal of plans and specifications. Plans and specifications for new construction must be submitted to the department for evaluation of function and fire protection. The department's approval must be obtained before beginning construction. Any modification during construction must be submitted to the department for review and shall be approved prior to the modification. A written narrative describing the intended use of the proposed construction must accompany the plans and specifications.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019.
General Authority: SDCL 34-12-13(1)(3).
Law Implemented: SDCL 34-12-13(1)(3).
44:70:10:38. Pipe requirements. Each piping system for potable water must be installed to eliminate any dead-end runs of piping. Before placing any potable water system in service, the piping system must be disinfected in accordance with article 20:54, and certification must be available from the installer showing the method used, date of installation, test procedure used to verify chlorine concentrations, and date the system was flushed and placed in service.
Any pipe covering, vapor barrier, and adhesive used must have a flame spread index of not more than twenty-five and a smoke emission factor of not more than fifty when tested in accordance with the ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Material.
Source: 38 SDR 115, effective January 9, 2012; 46 SDR 65, effective November 26, 2019; 50 SDR 19, effective August 30, 2023; 51 SDR 53, effective November 11, 2024.
General Authority: SDCL 34-12-13.
Law Implemented: SDCL 34-12-13.
Reference: ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials. Copies may be obtained at https://www.astm.org/e0084-23d.html. Cost: $119.00.
44:70:10:39. Water recreation facilities. Each water recreation facility operated by a facility and used by any resident or the public, must be designed, constructed, and maintained using the "Recommended Standards for Swimming Pool Design and Operation," 1996 edition.
A facility shall collect and submit at least one water sample weekly for each swimming pool, spa, or other water recreational facility under the owner's or operator's control to an EPA-certified laboratory for bacteriological analysis. The owner or operator shall report any unsafe water sample test results to the department within three days after receipt of such test results. Upon the receipt of an unsafe water sample, the facility must submit two consecutive negative samples to the department to confirm treatment procedures have eliminated the contamination. If a resample test is positive, the facility must close the affected water recreational facility and submit two consecutive negative samples prior to allowing use of the affected water recreational facility. The facility shall use a colorimetric test kit for the monitoring and adjusting of disinfectant levels and pH in a swimming pool, spa, or other water recreational facility. The facility shall maintain a daily log of disinfectant levels and pH.
Source: 38 SDR 115, effective January 9, 2012; 50 SDR 19, effective August 30, 2023.
General Authority: SDCL 34-12-13(1)(14).
Law Implemented: SDCL 34-12-13.
Collateral Reference: "Recommended Standards for Swimming Pool Design and Operation." Copies are available at no cost at https://doh.sd.gov/documents/Food/standardsforswimmingpooldesign.pdf.